120W 高压电源
斯派曼PCM 系列是交流输入,120W 高压电源模块。其特点:前端功率因数校正,提供0.99 功率因数以及通用的输入电压(85Vac 至265Vac) 能力。固定极性的模块(在订购时指定正极性或负极性) 特点:自动切换电压和电流调节,使其适合敏感负载应用。PCM 系列连同电弧和短路保护的强健设计,允许在极其苛刻的环境下工作。
典型应用:
- 静电纺丝
- 高压绝缘试验测试
- 探测器阵列
- 电泳
- 电缆测试
规格
(Ref. 128006-001 REV. T)
Input:
85-265Vac, 47-63Hz @ 1.8A, power factor corrected.
UL® rated for 85-250Vac input for 1kV to 5kV models.
Power Factor (Typical):
FL: 0.99
NL: 0.98
Efficiency:
80 to 85%, typical
Output:
11 models from 1kV to 70kV. Positive or negative polarity outputs, specify at time of order.
Voltage Regulation:
Load: 0.01% of output voltage, no load to full load.
Line: ±0.01% for ±10% change in input voltage.
Current Regulation:
Load: 0.01% of output current from 0 to rated voltage. Line: 0.01% of rated current over specified input range.
Ripple:
0.1% p-p of maximum output voltage.
Voltage Stability:
0.02% per 8 hours.
Temperature Coefficient:
100ppm per °C, voltage or current regulated.
Environmental:
Operational: 0 to 40°C
Storage: -40°C to +85°C
Humidity: 0 to 90%, non-condensing
Dimensions:
1kV to 50kV: 3.65”H x 5”W x 9”D (9.27cm x 12.7cm x 22.9cm).
60, 70kV: 3.65”H x 5”W x 11”D (9.27cm x 12.7cm x 27.9cm).
Weight:
7 pounds (3.18kg)
AC Input Connectors:
IEC320 with mating cable.
Interface Connector:
15 pin D connector.
HV Output Cable:
Spellman Delrin type connector with 36” (91.4cm) shielded cable.
Front Panel Ground Connection:
Threaded 8-32 ground stud
Regulatory Approvals:
Compliant to EEC EMC Directive. Compliant to EEC Low Voltage Directive. UL/CUL recognized, File E148969 (up to 60kV only). RoHS Compliant
PCM SELECTION TABLE
Maximum Rating | Model Number | |
---|---|---|
kV | mA | |
1 | 120 | PCM 1*120 |
3 | 40 | PCM 3*120 |
5 | 24 | PCM 5*120 |
10 | 12 | PCM 10*120 |
15 | 8 | PCM 15*120 |
20 | 6 | PCM 20*120 |
30 | 4 | PCM 30*120 |
40 | 3 | PCM 40*120 |
50 | 2.4 | PCM 50*120 |
60 | 2.0 | PCM 60*120 |
70 | 1.7 | PCM 70*120 |
*Specify “P” for positive polarity or “N” for negative polarity.
PCM D CONNECTOR 15 PIN
Pin | Signal | Parameters |
---|---|---|
1 | Remote mA Program | 0 to 10Vdc = 0 to 100% of rated output |
2 | Remote kV Program | 0 to 10Vdc = 0 to 100% of rated output |
3 | High Voltage Enable/Inhibit | Open = HV Inhibit, Ground = HV ON |
4 | mA Monitor | 0 to 10Vdc = 0 to 100% of rated output |
5 | Interlock Return | Connect to pin 6 to close interlock circuit |
6 | Interlock Out | Connect to pin 5 to close interlock circuit |
7 | kV Monitor | 0 to 10Vdc = 0 to 100% of rated output |
8 | Local kV Program | Multi-turn front panel pot (screwdriver) |
9 | Power Supply Fault | 0Vdc = No Fault, +15Vdc @ 1mA = Fault |
10 | +10Vdc Reference | +10Vdc @ 1mA maximum |
11 | Signal Ground | Signal Ground |
12 | Spare | No Connection |
13 | Spare | No Connection |
14 | Spare | No Connection |
15 | Local mA Program | Multi-turn front panel pot (screwdriver) |
表和图
DIMENSIONS: in.[mm]
SIDE VIEW
TOP VIEW
BACK VIEW
Frequently Asked Questions
What Is a Safe Level of High Voltage?
Where Can I Obtain Information on High Voltage Safety Practices?
What Kind of High Voltage Connector Do You Use on Your Supplies?
What Do You Mean That the Output Side of the High Voltage Cable on Most Standard Products Is “Unterminated”?
How Should I Ground Your Supply?
Why Is Arcing an Issue for a High Voltage Power Supply?
Application Notes AN-19 – High Voltage Cable Lengths Discussed